Executive standard: GB3836.1、GB3836.2、GB3836.3、GB12476.1、Q/HD209-2013etc.
Explosion-proof mark: ExdⅡCT6Gb/DIP A21 TA,T6
Rated voltage: AC220V 50/60Hz
Ambient temperature: -30℃~+50℃
IP: IP66
Introduction device: G3/4”Inlet specification, suitable for Φ11~Φ14mm cable
Terminals: 2.5mm2 wire for reliable installation
Installation method: Direct Ceiling Type (x1), Indirect Ceiling Type (x2), Direct Wall Mounting (b1), Indirect Wall Mounting (b2), Guardrail Type (h), Ring Type (dh), Boom Type (g)
Whole lamp power: 60W、70W、80W、90W、100W
Weight: 8.0Kg
◆ Copper-free Aluminum housing with high voltage electrostatic spraying surface.
◆ Stainless steel exposed fastener with high anti-correction performance.
◆ Toughened glass cover stands 4J impact and resistant to temperature changes ,with high lighting transmittance .
◆ Power driver and led source are in different cavity which assure heat of led source will not transmit to the power driver cavity.
◆ Entire explosion proof structure and spigot flameproof joint, assure reliable explosion-proof performance.
◆ Patent optical design with wide beam angle.
◆ Professional optical design and quadratic light distribution ,special design of reflector result in high uniformity of illumination and reasonable distribution.
◆ Special constant current power driver can assure wide voltage input and output constant current. With short-circuit and overvoltage protection,over-temperature protection etc.
◆ Adopted imported LED chips, reasonable arrangement ,soft and uniform lighting, longer working time and eco-friendly.
◆ Patent fins heat-dissipation structure increased the cooling surface area. Air convection slot design can make use of air flow to assure high quality heat-dissipation performance and longer working time .
Type | Rated power(W) | Rated voltage(V) | Lamp efficiency lm/W | Ex-mark | IP |
BHD8610-60 | 60 | AC220 | 90 | ExdⅡCT6Gb ExtdA21IP66T80℃ | IP66 |
BHD8610-70 | 70 | AC220 | 90 | IP66 | |
BHD8610-80 | 80 | AC220 | 90 | IP66 | |
BHD8610-90 | 90 | AC220 | 90 | IP66 | |
BHD8610-100 | 100 | AC220 | 90 | IP66 |
Applications
Applied to hazardous areas ,such as oil fields, oil refinery, chemical industry and military base and offshore oil platform ,wharf etc. Gas explosion environment : Zone 1 and Zone 2 and dust explosion environment : Zone 21 and Zone 22. Class ⅡA、ⅡB、ⅡC gas explosion environment. Temperature class: T1-T6.